Unused energy (grid limitation)

Energy above the grid export limit

Unit kWh/kWp

What this step does

The energy the grid power limitation removes, shown on its own row when the limitation is accounted as a separate loss (Losses tab). The inverters lower their ceiling so that the grid connection stays within the limit, and the row is the inverter output without that ceiling minus the output with it. Without the separate row, the same energy counts in Inverter Loss over nominal inv. power.

The math

  1. Running total
  2. Loss at a timestep
Eafter=Ebefore−Erow,Erow=Δt1000 PDC∑iLi(1)E_{after} = E_{before} - E_{row},\qquad E_{row} = \frac{\Delta t}{1000\,P_{DC}}\sum_i L_i \tag{1} Li=Ninv (Pinv,iu−Pinv,i)(2)L_i = N_{inv}\,\left(P^{u}_{inv,i} - P_{inv,i}\right) \tag{2}

where

Symbol Meaning Unit
EbeforeE_{before} the running total of the loss diagram before this row kWh/kWp
EafterE_{after} the running total after this row kWh/kWp
ErowE_{row} the row taken as a loss kWh/kWp
Δt\Delta t the length of one timestep hours
PDCP_{DC} the DC nameplate of the system kWp
LiL_i the power lost at timestep ii over the whole system W
NinvN_{inv} the number of inverters —
Pinv,iuP^{u}_{inv,i} the output one inverter would deliver at timestep ii without the grid ceiling W
Pinv,iP_{inv,i} the output of one inverter at timestep ii with the ceiling W

Reading the number

A loss, negative. Zero without a limit; a limit well below the inverters' nameplate on a utility system can cost several percent, and a rooftop system with an export limit loses in the same way. The limit relative to the system's peak AC output sets it.

API

loss.grid_limit