pvperfsolar performance modeling

Reference

Loss row

Night consumption

Standby power the inverter draws while it is not producing

Unit kWh/kWp

What this step does

The inverter draws a small standby power on every timestep in which it does not produce. The row takes it from the inverter output. It is zero when the transformer night disconnect is on (Losses tab).

The math

  1. Running total
  2. Loss at a timestep
Eafter=Ebefore−Erow,Erow=Δt1000 PDC∑iLi(1)E_{after} = E_{before} - E_{row},\qquad E_{row} = \frac{\Delta t}{1000\,P_{DC}}\sum_i L_i \tag{1} Li=Ninv Pnt(the inverter does not produce)(2)L_i = N_{inv}\,P_{nt} \quad (\text{the inverter does not produce}) \tag{2}

where

Symbol Meaning Unit
EbeforeE_{before} the running total of the loss diagram before this row kWh/kWp
EafterE_{after} the running total after this row kWh/kWp
ErowE_{row} the row taken as a loss kWh/kWp
Δt\Delta t the length of one timestep hours
PDCP_{DC} the DC nameplate of the system kWp
LiL_i the power lost at timestep ii over the whole system W
NinvN_{inv} the number of inverters —
PntP_{nt} the night consumption of one inverter W

Reading the number

A loss, negative: a few hundredths of a percent on utility and rooftop systems alike. A higher standby draw and longer nights make it larger.

References

  1. King, Gonzalez, Galbraith & Boyson 2007, Performance Model for Grid-Connected Photovoltaic Inverters, Sandia report SAND2007-5036