Loss row
Mismatch loss, modules and strings
Modules and strings that do not match each other
Unit kWh/kWp
What this step does
The power lost because the modules of a string, and the strings of an inverter, do not share one maximum-power point. The module mismatch and the string mismatch combine into one flat fraction of the array energy.
The math
where
| Symbol | Meaning | Unit |
|---|---|---|
| the running total of the loss diagram before this row | kWh/kWp | |
| the running total after this row | kWh/kWp | |
| the row as a loss | kWh/kWp | |
| the module mismatch loss input, a fraction | — | |
| the string mismatch loss input, a fraction | — |
Reading the number
A loss, negative. With the common design values, 2 % for the modules and 0.15 to 0.5 % for the strings, it is about 2 to 2.5 % on utility and rooftop systems alike. The two inputs alone set it.
API
loss.mismatch
Symbols follow the symbol registry.