pvperfsolar performance modeling

Reference

Loss row

Medium voltage transfo loss

No-load and load losses of the medium-voltage transformers

Unit kWh/kWp

What this step does

The loss of the medium-voltage transformers: the no-load loss drawn while a transformer is connected and the load loss that grows with the square of the power through it. pvperf models one medium-voltage transformer per inverter. The row acts on the inverter output.

The math

  1. Running total
  2. Loss at a timestep
Eafter=Ebefore−Erow,Erow=Δt1000 PDC∑iLi(1)E_{after} = E_{before} - E_{row},\qquad E_{row} = \frac{\Delta t}{1000\,P_{DC}}\sum_i L_i \tag{1} Li=Ninv(fFe Pref [connected]+fCuPref PF2 Pc,i2)(2)L_i = N_{inv}\left(f_{Fe}\,P_{ref}\,[\text{connected}] + \frac{f_{Cu}}{P_{ref}\,\text{PF}^2}\,P_{c,i}^2\right) \tag{2}

where

Symbol Meaning Unit
EbeforeE_{before} the running total of the loss diagram before this row kWh/kWp
EafterE_{after} the running total after this row kWh/kWp
ErowE_{row} the row taken as a loss kWh/kWp
Δt\Delta t the length of one timestep hours
PDCP_{DC} the DC nameplate of the system kWp
LiL_i the power lost at timestep ii over the whole system W
NinvN_{inv} the number of inverters —
fFef_{Fe} the no-load loss, as a fraction of the reference power —
PrefP_{ref} the AC power reference of one inverter: its AC nameplate, or its share of the array's STC reference power, the DC nameplate reduced by the module and string mismatch derates (the Model tab's AC power reference step sets which) W
[connected][\text{connected}] 1 while the transformer is connected; 0 on a timestep without export when the night disconnect is on —
fCuf_{Cu} the load loss at the reference power and unit power factor, as a fraction of the reference power —
PF\text{PF} the power factor —
Pc,iP_{c,i} the power the load loss is computed on: the output of one inverter; when the Model tab's AC resistive reference step is set to Cascade, the power after its AC wiring W

Reading the number

A loss, negative. About 1 % over a year for the usual fractions on a utility system; zero on a rooftop system without its own transformer. The no-load part weighs more at low load and at night.

References

  1. IEC 60076-1:2011, Power transformers, Part 1: general (no-load and load losses)