Loss row
Change at the POI from storage
The change in grid injection a DC-coupled battery causes
Unit kWh/kWp
What this step does
With DC coupling, the change in the system's energy injected into the grid that the battery causes. The battery charges on the DC bus, first from the DC power above the inverter's capability and then, when its strategy calls for more, from the power below it, and delivers DC power into the inverter's spare capability. The row measures the effect at the grid connection, after the inverter efficiency and the AC losses have been applied to the combined input.
The math
- The row on the running total
- The surplus, the first charge source, while the inverter sits at its capability (its AC ceiling or its input-current limit)
- The charge of each strategy, and the part of it taken below the capability
- The inverter's DC input with the battery
- The output of an inverter that ran without the battery
- The output while the input-current limit sets the capability (the inverter's input follows the bus voltage)
- The output of an inverter the battery starts (no array output, night)
where
| Symbol | Meaning | Unit |
|---|---|---|
| the running total after this row | kWh/kWp | |
| the running total before this row | kWh/kWp | |
| the change | kWh | |
| the system DC nameplate | kWp | |
| the system's grid injection with the battery at timestep : the run's AC losses applied to | kW | |
| the system's grid injection before the battery at timestep | kW | |
| the length of one timestep | h | |
| the system's DC surplus above the inverters' capability | kW | |
| the number of inverters | — | |
| one inverter's array DC power at bus voltage | kW | |
| the DC bus voltage of timestep (the maximum-power voltage held inside the MPPT window while the inverter sits at its capability) | V | |
| one inverter's DC capability at bus voltage : the most DC input it takes there | kW | |
| the DC input at which the inverter output reaches its ceiling at bus voltage | kW | |
| the inverter's maximum DC input current | A | |
| the inverter's AC output at a DC input and voltage | kW | |
| the inverter's AC ceiling at timestep | kW | |
| the DC power taken to charge the battery at timestep | kW | |
| the charge power that fills the battery within timestep : the room left below the state-of-charge ceiling divided by | kW | |
| the battery's power rating: it caps the power delivered on discharge and the power stored in the cells on charge | kW | |
| the charge efficiency, one minus half of the round-trip loss | — | |
| the clipped surplus expected over the lookahead window after timestep , divided by | kW | |
| the DC power the inverters take from the array at timestep , summed over the system, which a charge below the capability can divert | kW | |
| the DC power diverted to charging below the capability | kW | |
| one inverter's DC input with the battery | kW | |
| one inverter's DC input without the battery (its capability while it sits at it) | kW | |
| the power drawn from the cells at timestep | kW | |
| the discharge efficiency, one minus half of the round-trip loss | — | |
| one inverter's output with the battery | kW | |
| one inverter's output without the battery | kW | |
| the bus voltage with the battery: between and the inverter's operating voltage without the battery when the battery takes part of the surplus, otherwise | V | |
| the output the battery's power alone gives | kW |
Reading the number
Positive when the recovered clipping outweighs the battery's conversion losses, negative otherwise. Under the clip-capture dispatch (storage.dispatch clip), a system whose inverters reach their AC ceiling or their input-current limit, typically at a DC-to-AC ratio of 1.3 to 1.5, gains a few percent of the solar total. Where the current limit binds, the capture also lowers the inverter's output in its hour, and the row is the net of the two. The daily full cycle and timed discharge dispatches also move production the inverter could have delivered, so their conversion losses can make the change negative. It is zero under clip capture on a system whose inverters reach neither limit, and it follows the same proportions on a rooftop system. At night a discharge too small to start the inverters gives no output, and the energy drawn from the cells for it is lost. A night hour in which the battery's output passes the auxiliaries' threshold (Losses tab) draws the daytime auxiliaries on top of the night ones.
References
- Denholm, Eichman & Margolis 2017, "Evaluating the Technical and Economic Performance of PV Plus Storage Power Plants", NREL/TP-6A20-68737
- DiOrio, Denholm & Hobbs 2020, "A model for evaluating the configuration and dispatch of PV plus battery power plants", Applied Energy 262 114465