Energy diverted to storage

AC energy taken from the grid injection to charge the battery

Unit kWh/kWp

What this step does

With AC coupling, the AC energy taken from the system's grid injection to charge the battery, metered before the charge loss. It acts on the grid energy. With DC coupling the row is replaced by Change at the POI from storage.

The math

  1. The row on the running total
  2. Clip capture
  3. Daily full cycle, outside the scheduled hours or with the battery at its floor
  4. Timed discharge, outside the window
Eafter=Ebefore−EchgPDC,Echg=∑ici Δt(1)E_{after} = E_{before} - \frac{E_{chg}}{P_{DC}},\qquad E_{chg} = \sum_i c_i\,\Delta t \tag{1} ci=min⁡ ⁣(pi−Ptgt, Hi, Pbatηc)when pi>Ptgt(2)c_i = \min\!\left(p_i - P_{tgt},\ H_i,\ \frac{P_{bat}}{\eta_c}\right) \quad \text{when } p_i > P_{tgt} \tag{2} ci={min⁡ ⁣(xi, Hi, Pbatηc)xi+Fi≥Himin⁡ ⁣(pi, Hi−Fi, Pbatηc)otherwise(3)c_i = \begin{cases} \min\!\left(x_i,\ H_i,\ \frac{P_{bat}}{\eta_c}\right) & x_i + F_i \ge H_i \\ \min\!\left(p_i,\ H_i - F_i,\ \frac{P_{bat}}{\eta_c}\right) & \text{otherwise} \end{cases} \tag{3} ci=min⁡ ⁣(pi, Hi, Pbatηc)when pi>0(4)c_i = \min\!\left(p_i,\ H_i,\ \frac{P_{bat}}{\eta_c}\right) \quad \text{when } p_i > 0 \tag{4}

where

Symbol Meaning Unit
EafterE_{after} the running total after this row kWh/kWp
EbeforeE_{before} the running total before this row kWh/kWp
EchgE_{chg} the energy taken to charge kWh
PDCP_{DC} the system DC nameplate kWp
cic_i the power taken to charge the battery at timestep ii kW
Δt\Delta t the length of one timestep h
pip_i the system's grid injection before the battery at timestep ii kW
PtgtP_{tgt} the interconnect target (storage.interconnect_limit_kw): the grid injection above which clip capture charges and up to which the battery discharges kW
HiH_i the charge power that fills the battery within timestep ii: the room left below the state-of-charge ceiling divided by ηc Δt\eta_c\,\Delta t kW
PbatP_{bat} the battery's power rating: it caps the power delivered on discharge and the power stored in the cells on charge kW
ηc\eta_c the charge efficiency, one minus half of the round-trip loss —
xix_i the surplus above the target, max⁡(0, pi−Ptgt)\max(0,\ p_i - P_{tgt}) kW
FiF_i the surplus energy expected over the lookahead window after timestep ii, divided by Δt\Delta t kW

Reading the number

A loss, negative. With clip capture it is the production above the target that the battery can hold: a few percent of the solar total for a system that often exports at its connection limit, under 1 % where the injection rises little above the target. It cannot exceed the injection above the target in a run without the battery (series p_grid_w with include_series), and a capacity above the largest daily total of that surplus is never filled. With daily full cycle or timed discharge it is close to one usable capacity a day. A battery of half the AC nameplate for 4 hours then takes about 730 h times the AC nameplate a year: a third to a half of the solar total for a utility plant, the larger share where the system yields less energy per kW of AC nameplate, and about half for a rooftop system with a low DC-to-AC ratio. A small battery, a high target or a battery kept full make it small.

References

  1. DiOrio, Dobos & Janzou 2015, "Technoeconomic Modeling of Battery Energy Storage in SAM", NREL/TP-6A20-64641

API

storage.charged

Symbols follow the symbol registry.